Interactive 3D CFD Study Audited Physics · Issue 3 (v3) OpenFOAM v2406 · 3D Buoyant RANS Mass Err ±0.000% · Heat Err ±0.20% 25 Nov 2026

Adding eight 41 kW GPU racks to an in-row-cooled data hall

Concept-stage airflow, N+1 failure, and infrastructure feasibility assessment for retrofitting eight 4x NVIDIA DGX H100 racks (326 kW total) into a 227 m2 slab-floor hall cooled by chilled-water in-row units.

Read this first: representative sample study. This report models a representative hard-floor data hall with chilled-water in-row coolers, built from published equipment datasheets (Vertiv Liebert CRV, NVIDIA DGX H100, ColdLogik CL23). It is not a survey of a live client site. The conclusions apply once the assumptions in Section 2 are confirmed or replaced with site measurements. Figures marked indicative (costs, plant, power, floor loading) are order-of-magnitude hand checks.
Interactive 3D CFD Digital Twin (Real OpenFOAM v2406 Fields)

Inspect the hall, thermal slices, and airflow streamlines across scenarios

LOADING...
18 C 27 C (A1 Rec) 30 C (GPU) 32 C (A1 Max) 48 C
Drag to orbit · Scroll to zoom · Click any rack or cooler
Section 01

Executive Summary

Question: Can eight racks of 4x NVIDIA DGX H100 (40.8 kW each, 326 kW total) replace eight 5 kW legacy racks at the east end of rows C and D, facing each other across hot aisle 2, and what must change?

Client Plan (No Upgrade)

Fails immediately on air

All 8 GPU racks exceed NVIDIA's 30 C limit (up to 47.5 C at C16) and 41 of 64 racks exceed ASHRAE 32 C (57 above 27 C). The hall needs 43.5 m3/s of air; existing units supply 27.3 m3/s.

Recommended: Option 1+

Hot-aisle containment + 10x CR050

Every rack stays at or below 23.2 C (GPU max 21.0 C) with all units running, and at or below 24.4 C (GPU max 22.0 C) with pod unit D12 failed. With backdraft dampers on rows A/B, the entire hall achieves full N+1 (≤ 24.8 C everywhere). Indicative capex: $0.43M to $0.71M.

Key Upgrade Note (Rows A & B)

Backdraft dampers unlock full N+1

Without dampers, losing existing unit B13 puts 1 legacy rack (A11) at 27.6 C (GPU max 22.6 C). Fitting backdraft dampers on rows A and B cuts B13 failure to 24.8 C with 0 racks above 27 C.

What we recommend: Option 1+

  • Contain hot aisle 2: Fit roof panels and sealed sliding end doors over hot aisle 2, with blanking panels and rail seals in every rack.
  • Add 6 new CR050 units: Install six 600 mm chilled-water in-row coolers (Liebert CRV CR050 class, 6,000 CFM, 53 kW) at C11, C12, C19, D11, D12, and D19. Six 5 kW legacy racks (30 kW IT) leave the hall.
  • Upgrade 4 adjacent units: Replace the four CR040 units flanking the GPU bay (C13, C18, D13, D18) with CR050 class units.
  • Fit backdraft dampers on rows A and B + fan controls: Run pod fans on hot-aisle differential pressure control (0 to -2 Pa), run rows A and B fans at 100%, and fit backdraft dampers on the eight rows A and B units so the entire hall achieves full N+1 under 27 C.

Design rule discovered: In the contained pod, installed in-row airflow with the largest unit out should be at least 1.05x the rack airflow at NVIDIA's 157 CFM/kW design figure (Option 1+ gives 1.16x all running, 1.06x with one out). Option 1 (four new units, 0.80x ratio) fails at design GPU airflow with 11 racks above 27 C and GPU inlets hitting 30.5 C. Option 2 (active rear doors) passes with all units running (26.1 C), but puts 5 legacy racks above 27 C (worst 30.5 C) when B13 fails without dampers, still leaves 1 rack at 27.5 C with dampers, and leaves only 0.57 m of hot-aisle clearance on the client layout.

Five decisions required from the operator

  1. Rack positions: Give up six positions and relocate 30 kW of legacy IT (Option 1+), or keep them with Option 2 (staggered rear doors plus backdraft dampers and untested center cold-aisle containment).
  2. Confirm 100% GPU airflow with NVIDIA: Obtain DGX H100 airflow at 100% fan PWM and site inlet temperature. If well below 1,601 CFM per system, fewer new units may suffice.
  3. Rows A and B dampers: Fit backdraft dampers on the eight rows A and B coolers to achieve full hall-wide N+1 (≤ 24.8 C everywhere), or accept 1 legacy rack reaching 27.6 C if B13 fails.
  4. Site altitude: With sealed doors in audited v3 physics, worst GPU inlet under D12 failure is 22.0 C (22.8 C under B13 failure), giving a 2.2 to 3.0 K margin even against NVIDIA's stricter 25 C limit above 1,000 ft.
  5. Plant and power: Confirm up to +340 kW N+1 chilled-water plant capacity (+15 l/s), +260 to 290 kW IT UPS/generator headroom, and slab floor load rating (9.8 kN/m2 under 600 mm GPU racks).
Section 02

Assumptions for Sign-Off

Each line must be confirmed or replaced with actual site data. The final column states what changes if the site differs.

# Item Value Assumed Basis If Your Site Differs
A1Room18.0 x 12.6 m, 3.6 m flat ceiling, slab floor, no plenumsRepresentativeCeiling return or taller room alters hot-air path: re-run
A2Rows & aisles4 rows of 20 (600 x 1200 mm); cold 1.6/1.8/1.6 m; hot 1.4 mRepresentativeNarrower hot aisles rule out facing rear doors (G5)
A3Existing cooling16 Vertiv Liebert CRV CR040 chilled-water in-row units (pos 3, 8, 13, 18)RepresentativeOther models require re-rating airflow and coil capacity
A4Existing fan speed88% rated airflow; 20 C supply airRepresentativeResult follows airflow ratio (Sec 4.1), not percentage
A5CR040 datasheet46.3 kW net sensible at 35 C ret / 7.2 C water; 3,620 CFMVertiv SL-71133 R10/26CR040RC web page lists 3,325 CFM (8% lower air ratio)
A6Chilled water7.2 C supply, 5.6 K riseRating conditionWarmer water lowers in-row sensible capacity
A7Legacy racks64 x 5.0 kW, 12 K rise (0.35 m3/s each), 320 kW totalRepresentativeReplace with measured PDU loads by position
A8GPU racks8 x (4x DGX H100, 10.2 kW max) = 40.8 kW/rack at C14-17, D14-17Client plan; NVIDIA guide800 mm racks shift layout; B200 requires a new study
A9GPU airflow157 CFM/kW = 1,601 CFM/system (3.02 m3/s per rack, 11.2 K rise)NVIDIA DGX SuperPOD H100 Design GuideDecides Option 1 vs Option 1+. Confirm 100% PWM flow with NVIDIA (1,105 CFM published at 80% PWM)
A10Rack leakage5% of front face open area (blanking + rail seals), Cd = 0.6Upsite AisleLok CFD studyUnblanked racks leak up to 40% recirculation
A11Failed in-row unitOpen resistive path (K = 20 velocity heads, ~24 Pa at rated flow)Bounding case (no damper)Backdraft dampers make row B failures milder (Sec 4.4)
A12In-row capacityLinear in (return - water) x airflow^0.8; CR050 on conservative 12.8 C ratingSingle-point datasheetPeak load stays at 92% across all cases; confirm with Vertiv selection
A13Rear door (Opt 2)ColdLogik CL23 active door, 415 mm deep, 20 C leaving airCL23 datasheet~45 kW duty at 31 C on-coil; requires ~14 C secondary water
A14Site altitudeBelow 305 m (1,000 ft)UnknownAbove 1,000 ft, NVIDIA limit drops to 25 C (zero margin)
A15Plant & powerSpare capacity per Section 6 gatesUnknownVerify chilled water, electrical, UPS, and slab capacity
Section 03

The Hall and the Options

Recommended layout Option 1+ showing GPU racks, CR040 and CR050 coolers, and contained hot aisle 2
Figure 1. Recommended layout (Option 1+). Grey: existing 5 kW racks. Pink: 40.8 kW GPU racks. Light blue: existing CR040 coolers. Dark blue: CR050 coolers (6 new, 4 replacing CR040). Shaded: contained hot aisle 2.
Case Changes From Today Hall Air Ratio (Cooler / Rack) Contained Pod Ratio (Rows C, D)
Existing hallNone (fans 88%)24.1 / 22.1 = 1.09-
Client plan8 GPU racks at C14-17, D14-17; fans 100%27.3 / 43.5 = 0.63-
Option 1 (Issue 1)Hot-aisle 2 containment; 4 new CR050 at C12, C19, D12, D1938.7 / 42.2 = 0.9225.0 / 31.1 = 0.80
Option 1+ (Recommended)Containment; 6 new CR050 + 4 CR040 swapped to CR050; A/B fans 100%48.8 / 41.5 = 1.1835.2 / 30.4 = 1.16 (1.06 N+1)
Option 2 (Rear doors)Active rear doors on 8 GPU racks (client layout), 20 C leaving, fans 100%27.3 / 43.5 (20 C doors)-
Option 2 (Staggered)Row D GPU racks shifted to D04-07 so doors do not face each otherSame-

Every case is judged by the warmest 0.4 m vertical band on each rack's front face against ASHRAE Class A1 (27 C recommended, 32 C allowable) and NVIDIA's 30 C DGX H100 inlet limit (25 C above 1,000 ft).

Section 04

CFD Findings and Option Ranking

Comparison of all options with all units running
Figure 2. All units running. Left: warmest GPU and legacy rack inlet. Center: racks above 27 C and 32 C. Right: peak in-row cooler load against rated capacity.

4.1 Existing hall baseline

In-Row Fan SpeedAir RatioRacks > 27 CWarmest Inlet
88% (assumed today, v3)1.091130.2 C (D10)
100% (v3)1.24025.8 C (A11)

Top-of-rack overheating happens whenever total in-row airflow drops below roughly 1.2x rack demand. Raising existing fans from 88% to 100% removes all 11 warm racks in the baseline hall.

4.2 Client plan fails because the hall runs out of air

Client plan rack inlet temperature map
Figure 3. Client plan (no cooling upgrade, audited v3): warmest inlet band on every rack and percentage load on each in-row cooler. All 8 GPU racks exceed 30 C (worst 47.5 C at C16); 57 racks exceed 27 C and 41 racks exceed 32 C.
Client plan vertical thermal cross-sections
Figure 4. Client plan cross-sections: across rows through the GPU racks (top) and along hot aisle 2 (bottom). The GPU bay discharges 24 m3/s into a hot aisle whose four adjacent coolers draw only 6.8 m3/s; hot air above 50 C floods the ceiling and drops into every cold aisle.

4.3 Why Issue 1's Option 1 fails at NVIDIA design airflow

Adding only four CR050 units yields a contained pod air ratio of 0.80x at NVIDIA's 157 CFM/kW minimum. The contained hot aisle pressurizes to +55 Pa and pushes hot exhaust out of door and rack leakage paths, driving 11 racks above 27 C and GPU inlets to 30.5 C (exceeding NVIDIA's 30 C limit).

4.4 Option 1+ (Recommended): thermal performance and failure matrix (v3)

Option 1+ rack inlet map with all units running
Figure 5. Option 1+ with all units running (v3): every rack in the hall stays at or below 23.2 C (GPU max 21.0 C), with peak cooler load at 86% (C19).
Option 1+ worst pod failure D12
Figure 6. Option 1+ with pod unit D12 failed (v3): warmest inlet 24.4 C (D20), warmest GPU 22.0 C, zero racks above 27 C, peak cooler load 88% (C18).
Option 1+ Case (Audited v3)Warmest InletWarmest GPURacks > 27 CPeak Cooler
All running, fans 100%23.2 C (A20)21.0 C086% (C19)
D12 failed (worst pod unit)24.4 C (D20)22.0 C088% (C18)
B13 failed (row B, no damper)27.6 C (A11)22.6 C187% (C19)
B13 failed (backdraft damper closed)24.8 C (B16)22.8 C087% (C19)

4.5 Option 2 (Active Rear Doors) and Head-to-Head Ranking

Single-failure comparison between Option 1+ and Option 2
Figure 7. Single-failure comparison (audited v3): Option 1+ (left) against Option 2 rear doors (right). Option 1+ with backdraft dampers achieves 0 racks above 27 C across all failures; Option 2 reaches 30.5 C (5 racks above 27 C) when B13 fails without dampers and 27.5 C (1 rack) with dampers.
CriterionOption 1+ (In-Row + Containment)Option 2 (Active Rear Doors)
All runningPass (all racks ≤ 23.2 C, GPU 21.0 C)Pass (all racks ≤ 26.1 C, GPU 23.8 C)
Pod failure (D12 off)Pass (worst 24.4 C, GPU 22.0 C, 0 > 27 C)Up to 29.7 C on pod failure (Issue 2 sensitivity)
Row B failure (B13)1 rack at 27.6 C; with dampers 0 racks > 27 C (24.8 C)5 racks > 27 C (30.5 C); with dampers 1 rack at 27.5 C
Rear door water lossNot applicable5 to 11 racks > 27 C (dampers do not help)
Worst GPU inlet22.8 C (passes 25 C high-altitude limit)25.7 C (exceeds 25 C high-altitude limit)
Rack positions lost6 legacy racks (30 kW relocated)0 (4 positions swapped if staggered)
Indicative capex$0.43M to $0.71M$0.28M to $0.61M (before dampers & center containment)
Next-gen GPU pathAir only (B200 requires more air again)CDU + secondary loop prepares for direct liquid cooling
Section 05

Equipment List, Commissioning & Acceptance Test

ItemQtySpecificationLocation
In-row cooler (CR050 class)6 new600 x 1100 x 2000 mm, ~342 kg, 6,000 CFM, 53.2 kW net sensible, EC fansC11, C12, C19, D11, D12, D19
In-row cooler (CR050 class)4 swapReplaces CR040 units flanking GPUs (removed units become spares)C13, C18, D13, D18
Hot-aisle containment1 aisleRoof panels (~12.4 x 1.4 m at 2.0 m) + two 1.4 m sliding end doorsHot aisle 2
Blanking & rail sealsHall-wideTarget leakage at or below 5% of rack faceRows C, D (all racks)
Backdraft dampers (opt.)8Gravity or motorized damper closing when fans stopRows A & B coolers
Differential pressure sensors2Integrated with pod in-row fan control (0 to -2 Pa target)Hot aisle 2 ends
Chilled-water branches10Isolation valves, flex connections, ~DN100 header extension (+15 l/s)Rows C, D loop
GPU rack power32 PDUs60 A 415 V 3-phase (43 kW nameplate), 2 per feed, A+B per rack8 GPU racks

Commissioning set points and acceptance test

  • Set points: 20 C supply air; rows A and B fans at 100%; pod fans on hot-aisle pressure at 0 to -2 Pa (80% minimum speed); GPU inlet alarm at 27 C.
  • Load-bank acceptance test: Run load banks at both 40.8 kW and 3.0 m3/s airflow per GPU position (heat alone does not test airflow shortage). Trip D12, D18, C18, and open containment doors; confirm GPU inlets ≤ 27 C. Trip B13 and verify legacy racks stay below 32 C allowable.
Section 06

Infrastructure Feasibility Gates (G1 to G9)

Order-of-magnitude hand checks against published typical figures. Confirm each gate against actual building records before ordering hardware.

GateRequirementOption 1+Option 2 (Rear Doors)
G1 Chilled-water plantIT + fan heat (N+1 chillers)~700 kW total (+340 kW upper bound; ~670 kW on pressure control), +15 l/s~670 kW total (+310 kW); ~370 kW via secondary loop
G2 Water distributionPiping & dew point10 live-loop connections (~DN100 header)N+1 CDUs + ~14 C secondary loop (avoids door condensation)
G3 Electrical & UPSIT power + PDU redundancy+256 kW net IT; 4x 60 A 415 V PDUs/rack; confirm 3/6 PSU cap with NVIDIA+286 kW net IT; same per-rack PDU requirement
G4 Fan power & UPSThermal ride-through~122 kW max fan power; in-row fans & CHW pumps must sit on UPS~57 kW in-row + 6.4 kW doors; fans, doors, CDU pumps on UPS
G5 Space & clearanceNVIDIA ≥ 0.91 m aislePass (1.40 m hot aisle unchanged)Fail on client layout (0.57 m); Pass if staggered
G6 Rack positionsZero empty positions today6 legacy racks (30 kW) removed from hall0 positions lost
G7 Floor loadingSlab rating (often 7.2 kN/m2)9.8 kN/m2 on 600 mm racks (7.4 on 800 mm); confirm slab12.2 kN/m2 with wet door (9.1 on 800 mm)
G8 Altitude derating30 C ≤ 1k ft; 25 C > 1k ft22.0 to 22.8 C worst GPU (passes 25 C limit with 2.2 to 3.0 K margin)25.7 C worst GPU (exceeds 25 C above 1,000 ft)
G9 NoiseDGX H100 ~98.7 dB(A)Contained hot aisle becomes hearing-protection zoneOpen hot aisle requires hearing protection around bay
Section 07

Indicative Cost and 9-Step Live Phasing

Equipment and installation ranges are scaled from published list/street anchors (±50%) and exclude IT hardware, PDUs, UPS, and central chiller upgrades. Top-down sanity bound: published whole-retrofit benchmarks ($2M to $3M per MW including plant) imply $0.5M to $0.8M for 256 kW.

Cost ComponentOption 1+Option 2 (Staggered)
Equipment10x CR050 ($0.30M to $0.45M) + containment ($0.03M to $0.06M)8 doors ($0.08M to $0.16M) + N+1 CDU ($0.10M to $0.25M)
Install, piping, controls$0.10M to $0.20M$0.10M to $0.20M
Not pricedBlanking, rail seals, pressure sensors, header ext., contingencyBackdraft dampers, center aisle containment, blanking, contingency
Total (indicative ±50%)$0.43M to $0.71M$0.28M to $0.61M (incomplete scope)

Live-hall phasing sequence (Option 1+)

Ordered so every intermediate step leaves hall airflow no worse than today:

  1. 01
    Survey and sign-off: Confirm Section 2 assumptions, Section 6 plant/slab gates, and order equipment.
  2. 02
    Pipework: Fit 10 chilled-water branch valves via hot taps or planned out-of-hours isolations.
  3. 03
    Relocate six legacy racks: Migrate C11, C12, C19, D11, D12, and D19 out of the hall.
  4. 04
    Install six new CR050 units: Commission in vacated slots; pod airflow now exceeds baseline.
  5. 05
    Swap four CR040 units one at a time: Replace C13, C18, D13, D18 while maintaining surplus airflow.
  6. 06
    Fit sealing and containment: Install blanking panels, rail seals, roof panels first, end doors last.
  7. 07
    Remove eight legacy racks in GPU bay: Migrate 40 kW IT from C14 to C17 and D14 to D17.
  8. 08
    Load-bank acceptance test: Run full airflow + heat failure tests before GPUs arrive.
  9. 09
    Install and commission the eight DGX H100 racks.
Section 08

Accuracy, Validation & Solver Method

  • Published reference validation: The same OpenFOAM solver setup matched published low-density benchmarks within 1 to 2 K (RISE ICE Module 1 measured fronts 0.29 K MAE; de Boer three-code benchmark 1.0 K MAE). On a third small room's exhaust-side sensors, a related model read 2.5 K low on average and 6 K low at the top of the rack.
  • Unverified regimes: None of those reference rooms had 41 kW racks, rear doors, or contained in-row aisles. Accuracy at 41 kW per rack is unverified. Treat single-rack margins under 2 to 3 K as unproven (this applies to Option 1+'s 0.9 K margin to 27 C on D12 failure; it does not threaten the GPU racks' 5 K margin to 30 C).
  • Audited v3 physics improvements: Full 0.6 m rack faces preserved (96.7% face area intact, 100% across upper bands 1 to 4; calibrated 0.2 x 0.2 m bottom-corner rack leakage tunnels), sealed 1.4 m containment end doors with calibrated 3% porous door vents verified via live flux read-backs, and tighter SIMPLE pressure-velocity coupling (consistent yes, p_rgh relTol 0.01). Mass balance closes to ±0.000% and heat balance closes within ±0.20% across all 11 v3 runs.
  • Grid and transient checks: Baseline v3 runs used 0.2 m cells (~87k to 88k cells, steady buoyant k-epsilon RANS averaged over the last 2,000 of 4,000 iterations). Prior Issue 2 sensitivity checks verified stability across 0.1 m grid refinement (726k cells) and 400 s time-accurate PIMPLE solves.
  • Simplifications: Racks are uniform over five height bands; rack leakage is a 5% calibrated resistance path; rear doors hold 20 C leaving air; transient power transfers and humidity are not modelled.